Following table shows the M-35 Mix Designs as per IS-10262-2009, hope this helps all civil engineers here
CONCRETE MIX DESIGN |
||
As per IS 10262-2009 & MORT&H |
||
A-1 |
Stipulations for Proportioning | |
1 |
Grade Designation | M35 |
2 |
Type of Cement | OPC 53 grade confirming to IS-12269-1987 |
3 |
Maximum Nominal Aggregate Size | 20 mm |
4 |
Minimum Cement Content (MORT&H 1700-3 A) | 310 kg/m3 |
5 |
Maximum Water Cement Ratio (MORT&H 1700-3 A) | 0.45 |
6 |
Workability (MORT&H 1700-4) | 50-75 mm (Slump) |
7 |
Exposure Condition | Normal |
8 |
Degree of Supervision | Good |
9 |
Type of Aggregate | Crushed Angular Aggregate |
10 |
Maximum Cement Content (MORT&H Cl. 1703.2) | 540 kg/m3 |
11 |
Chemical Admixture Type | Superplasticiser Confirming to IS-9103 |
A-2 |
Test Data for Materials | |
1 |
Cement Used | Coromandal King OPC 53 grade |
2 |
Sp. Gravity of Cement | 3.15 |
3 |
Sp. Gravity of Water | 1.00 |
4 |
Chemical Admixture | BASF Chemicals Company |
5 |
Sp. Gravity of 20 mm Aggregate | 2.884 |
6 |
Sp. Gravity of 10 mm Aggregate | 2.878 |
7 |
Sp. Gravity of Sand | 2.605 |
8 |
Water Absorption of 20 mm Aggregate | 0.97% |
9 |
Water Absorption of 10 mm Aggregate | 0.83% |
10 |
Water Absorption of Sand | 1.23% |
11 |
Free (Surface) Moisture of 20 mm Aggregate | nil |
12 |
Free (Surface) Moisture of 10 mm Aggregate | nil |
13 |
Free (Surface) Moisture of Sand | nil |
14 |
Sieve Analysis of Individual Coarse Aggregates | Separate Analysis Done |
15 |
Sieve Analysis of Combined Coarse Aggregates | Separate Analysis Done |
15 |
Sp.Gravity of Combined Coarse Aggregates | 2.882 |
16 |
Sieve Analysis of Fine Aggregates | Separate Analysis Done |
A-3 |
Target Strength for Mix Proportioning | |
1 |
Target Mean Strength (MORT&H 1700-5) | 47N/mm2 |
2 |
Characteristic Strength @ 28 days | 35N/mm2 |
A-4 |
Selection of Water Cement Ratio | |
1 |
Maximum Water Cement Ratio (MORT&H 1700-3 A) | 0.45 |
2 |
Adopted Water Cement Ratio | 0.4 |
A-5 |
Selection of Water Content | |
1 |
Maximum Water content (10262-table-2) | 186 Lit. |
2 |
Estimated Water content for 50-75 mm Slump | 160 Lit. |
3 |
Superplasticiser used | 0.5 % by wt. of cement |
A-6 |
Calculation of Cement Content | |
1 |
Water Cement Ratio | 0.4 |
2 |
Cement Content (160/0.42) | 400 kg/m3 |
|
Which is greater then 310 kg/m3 | |
A-7 |
Proportion of Volume of Coarse Aggregate & Fine Aggregate Content | |
1 |
Vol. of C.A. as per table 3 of IS 10262 | 62.00% |
2 |
Adopted Vol. of Coarse Aggregate | 62.00% |
|
Adopted Vol. of Fine Aggregate ( 1-0.62) | 38.00% |
A-8 |
Mix Calculations | |
1 |
Volume of Concrete in m3 | 1.00 |
2 |
Volume of Cement in m3 | 0.13 |
|
(Mass of Cement) / (Sp. Gravity of Cement)x1000 | |
3 |
Volume of Water in m3 | 0.160 |
|
(Mass of Water) / (Sp. Gravity of Water)x1000 | |
4 |
Volume of Admixture @ 0.5% in m3 | 0.00168 |
|
(Mass of Admixture)/(Sp. Gravity of Admixture)x1000 | |
5 |
Volume of All in Aggregate in m3 | 0.711 |
|
Sr. no. 1 – (Sr. no. 2+3+4) | |
6 |
Volume of Coarse Aggregate in m3 | 0.441 |
|
Sr. no. 5 x 0.62 | |
7 |
Volume of Fine Aggregate in m3 | 0.270 |
|
Sr. no. 5 x 0.38 | |
A-9 |
Mix Proportions for One Cum of Concrete (SSD Condition) | |
1 |
Mass of Cement in kg/m3 | 400 |
2 |
Mass of Water in kg/m3 | 160 |
3 |
Mass of Fine Aggregate in kg/m3 | 704 |
4 |
Mass of Coarse Aggregate in kg/m3 | 1271 |
|
Mass of 20 mm in kg/m3 | 915 |
|
Mass of 10 mm in kg/m3 | 356 |
5 |
Mass of Admixture in kg/m3 | 2.00 |
6 |
Water Cement Ratio | 0.40 |
|
If you have a query, you can ask a question here.
WHAT WILL BE THE MIX DRSIGN FOR PUMPED CONCRETE
how be make proportion for pumped concrete
please send me the proper procedure of well foundation
how to calculate the amount of cement,sand,aggregate in a design mix of concrete for Rcc structure.i would be glad for the reply
Dear sir,
Please tell me What is the limit of Standard Deviation for concrete (cube Strength)
Thanks
Harish Adhikari
What will be the 7days strength for C35 concrete and which specification/standard can it be found/confirmed.
Thank you for giving Valuble note.
Is there any relation between coefficient of uniformity of sand used in the mixdesign to the strength of concrete cubes cast with it?
thnks for information
i want concrete cube MAXIMUM & MINMUM STRENGTH OF M-25 & M-35.
What are the environmental guide line for using M25,M30 & M40 concrete. Can it it be used in hot climate? How are the strength,shrinkage, cracks etc affected with variation of temperature? Please send the Q.C. for these grade of concrete to be adopted as per I.S. Specification to my email.
what is the estimated water content, how it can estimate.
what is the equivalent standard for C25/30 & what is the equivalent standard for BS t55s steel in India
Target strength =43.25(35+1.65*5) I have designed M35 using 350kg cement per cum, 2% plasticiser( conplast sp337at 1.5%wt of cement , JK 43 opc cement used . w/c =0.4 Sp gr of cement =2.92,Sp gr of ca=2.64, sp gr of fa =2.62 excellent result obtained pl try & reply pl read % of plasticiser as 1.50% of wt of cement
Could you please provide the difference between grade 35A(used for water retaining structures) and grade 35 concrete.
Thanks!
Please kindly send me M35 grade Mix Design weight basis as well as volumetric for Pile and quantity of aggregate & cement per cum of casting at my Email
dear sir,
please tell me what is maximum time of placing the concrete if cement content is 380kg/m3, w/c= .45, slump=150
Dear sir,
I wanted to know the 28 Mgpascal concrete admixture (cement, sand, gravel, water and slump) thanks
I want to know how cubes give maximum strength in manimum days
what is a design calculation of m35 concrete