M-30 Mix Designs as per IS-10262-2009

Posted in Mix Design | Email This Post Email This Post |
Print Friendly, PDF & Email

By
Raj Mohammad Khan

Following table shows the M-30 Mix Designs as per IS-10262-2009, hope this helps all civil engineers here

M-30 CONCRETE MIX DESIGN

As per IS 10262-2009 & MORT&H

A-1

Stipulations for Proportioning

1

Grade Designation M30

2

Type of Cement OPC 53 grade confirming to IS-12269-1987

3

Maximum Nominal Aggregate Size 20 mm

4

Minimum Cement Content (MORT&H 1700-3 A) 310 kg/m3

5

Maximum Water Cement Ratio (MORT&H 1700-3 A) 0.45

6

Workability (MORT&H 1700-4) 50-75 mm (Slump)

7

Exposure Condition Normal

8

Degree of Supervision Good

9

Type of Aggregate Crushed Angular Aggregate

10

Maximum Cement Content (MORT&H Cl. 1703.2) 540 kg/m3

11

Chemical Admixture Type Superplasticiser Confirming to IS-9103

A-2

Test Data for Materials

1

Cement Used Coromandal King OPC 53 grade

2

Sp. Gravity of Cement 3.15

3

Sp. Gravity of Water 1.00

4

Chemical Admixture BASF Chemicals Company

5

Sp. Gravity of 20 mm Aggregate 2.884

6

Sp. Gravity of 10 mm Aggregate 2.878

7

Sp. Gravity of Sand 2.605

8

Water Absorption of 20 mm Aggregate 0.97%

9

Water Absorption of 10 mm Aggregate 0.83%

10

Water Absorption of Sand 1.23%

11

Free (Surface) Moisture of 20 mm Aggregate nil

12

Free (Surface) Moisture of 10 mm Aggregate nil

13

Free (Surface) Moisture of Sand nil

14

Sieve Analysis of Individual Coarse Aggregates Separate Analysis Done

15

Sieve Analysis of Combined Coarse Aggregates Separate Analysis Done

15

Sp. Gravity of Combined Coarse Aggregates 2.882

16

Sieve Analysis of Fine Aggregates Separate Analysis Done

A-3

Target Strength for Mix Proportioning

1

Target Mean Strength (MORT&H 1700-5) 42N/mm2

2

Characteristic Strength @ 28 days 30N/mm2

A-4

Selection of Water Cement Ratio

1

Maximum Water Cement Ratio (MORT&H 1700-3 A) 0.45

2

Adopted Water Cement Ratio 0.42

A-5

Selection of Water Content

1

Maximum Water content (10262-table-2) 186 Lit.

2

Estimated Water content for 50-75 mm Slump 160 Lit.

3

Superplasticiser used 0.5 % by wt. of cement

A-6

Calculation of Cement Content

1

Water Cement Ratio 0.42

2

Cement Content (160/0.42) 380 kg/m3

Which is greater then 310 kg/m3

A-7

Proportion of Volume of Coarse Aggregate & Fine Aggregate Content

1

Vol. of C.A. as per table 3 of IS 10262 62.00%

2

Adopted Vol. of Coarse Aggregate 62.00%

Adopted Vol. of Fine Aggregate ( 1-0.62) 38.00%

A-8

Mix Calculations

1

Volume of Concrete in m3 1.00

2

Volume of Cement in m3 0.12

(Mass of Cement) / (Sp. Gravity of Cement)x1000

3

Volume of Water in m3 0.160

(Mass of Water) / (Sp. Gravity of Water)x1000

4

Volume of Admixture @ 0.5% in m3 0.00160

(Mass of Admixture)/(Sp. Gravity of Admixture)x1000

5

Volume of All in Aggregate in m3 0.718

Sr. no. 1 – (Sr. no. 2+3+4)

6

Volume of Coarse Aggregate in m3 0.445

Sr. no. 5 x 0.62

7

Volume of Fine Aggregate in m3 0.273

Sr. no. 5 x 0.38

A-9

Mix Proportions for One Cum of Concrete (SSD Condition)

1

Mass of Cement in kg/m3 380

2

Mass of Water in kg/m3 160

3

Mass of Fine Aggregate in kg/m3 711

4

Mass of Coarse Aggregate in kg/m3 1283

Mass of 20 mm in kg/m3 924

Mass of 10 mm in kg/m3 359

5

Mass of Admixture in kg/m3 1.90

6

Water Cement Ratio 0.42
Advertisements

We are thankful to Er. Raj M. Khan for sharing this information with us on engineeringcivil.com. We hope this would be of great significance to civil engineers.

More Entries :
Comments
  • mohankumar.badiger February 13, 2012 at 3:11 am

    thanks for your guidance about mix design sir…….

  • Tony February 22, 2012 at 5:03 am

    Dear sir,
    If i use the specific gravity -dry, for the calculations of mix design, is there any problem for the presentation?

    • Er. Raj M. Khan July 10, 2012 at 6:57 am

      No, You can not use the dry specific Gravity, because you have to maintain W/C ratio & After that the moisture correction is to be made. else the desired slump can not be achieved.

  • HEMRAJ May 11, 2012 at 1:30 pm

    which admixture will used in M30 grade concrete ,give ex.

  • surya June 13, 2012 at 11:44 am

    please give description about unit weight of m30

    • Er. Raj M. Khan July 10, 2012 at 6:58 am

      just add the concrete ingredients of m-30

    • sauvir singh November 24, 2012 at 7:32 am

      water =173.23 kg cement= 455.87kg fine aggregate (specific gravity2.67 =442.27 kg
      coarsse aggregate specific gravity (2.92) = 1405.69 kg

      unit wt of m30 after 28days curing is = 2650kg /cum in lab condition it may be deffer at site

  • Oryakhel June 13, 2012 at 2:46 pm

    thanks for every one helping each other

    • Er. Raj M. Khan July 10, 2012 at 6:58 am

      its my pleasure

  • pratik July 11, 2012 at 4:28 am

    Can you plz help me with m30 mix ratio in litres.it would be very helpful of you. Ithank you

  • Krishna rao July 21, 2012 at 2:47 am

    Very thankful to you sir

  • dilip swami October 7, 2012 at 7:20 am

    sir for making m-30 or m40 class paver which machine i purchase technically.thanks

  • kalyan kumar giri October 13, 2012 at 9:23 am

    dear, sir can u write me what are the ratio i used (cement, sand, stone dust,water or any chemical for making of solid bricks) which is harden and can be used for construction of building. i newly start production of cement solid brick for rural people which is cheaper then clay brick thankin you

  • Anil gupta October 29, 2012 at 6:13 am

    Can you plz help me with m30 mix ratio in kg.it would be very helpful of you. Ithank you

  • Atul kumar December 2, 2012 at 3:22 am

    Dear sir,
    If i use the specific gravity -dry, for the calculations of mix design, is there any problem for the presentation?

  • tarun jain February 6, 2013 at 8:35 am

    for the example that you have solved for m30 what’s the mix ratio sir

  • sivakumar February 12, 2013 at 1:27 am

    what is mix ratio for m30

  • tarun jain February 20, 2013 at 7:08 am

    am gettin 41.5 as strength at th7 day for m30 amd opc 53. is it correct

  • krutik tachak March 5, 2013 at 9:25 am

    can anyone tel me mix proportion for M30 in terms of ghamela ??? like at site i used normal concrete mixer . so wat do i need to tell to labour to pour in the materials

  • ER. SUSANTA KUMAR MISRA April 12, 2013 at 5:52 am

    This is very necessary for all civil engineers. Thanks to all.
    How can we calculate the Mix design for M-30 C.C keeping cement content constant ?

  • NIRVESH JAISWAL July 3, 2013 at 7:17 am

    can design mix concrete be converted into nominal mix concrete at work site for concrete grade more than M25 and above.

  • Dr.A.R.Majumdar July 23, 2013 at 10:49 am

    can i suggest some clarity and improvement?

  • Goutam kumar dutta July 30, 2013 at 1:15 am

    Dear sir can U write me the mixer machine mix m-30 site. pl. write me Box size. Thanking you

  • prakash gavhane October 2, 2013 at 12:04 am

    what is the ratio of concrete above m35,40,45& above?

  • Post a comment

1 2 3 4 5